Electrical scope
Confirm voltage, capacity, frequency, vector group and tap range against the project brief.


PRODUCT DETAIL / OIL-IMMERSED TRANSFORMERS
10kV / 0.4kV · Oil-immersed cooling · Fully sealed tank
01 / OVERVIEW
Read the supplied description before sharing project requirements.
We manufacture the S20 10kV Oil Immersed Transformer, a nextgeneration energysaving product. It delivers low loss, low noise and outstanding durability, supplying reliable and stable power for industrial, commercial and powerutility projects.
We design our S20 10kV Oil Immersed Transformer to meet modern energyefficiency and performance standards. We adopt highquality siliconsteel cores together with an innovative windingstructure design, which greatly cuts down both noload losses and load losses.
Its oilfullyimmersed cooling system delivers excellent heat dissipation. The transformer maintains stable operation even under heavyload conditions. Besides, our fullysealed tank design blocks moisture and oxidation. It extends service life and lowers maintenance workload.
Our S20 series transformers have been deployed worldwide in powergrid systems, industrial sites, commercial premises and infrastructure projects. Compact footprint, safe operation and strong overload capacity make the S20 series one of our most popular offerings. Customers benefit from its solid performance and favorable totalcostofownership over longterm operation.
PRODUCT / APPLICATION VIEW
Product photography and application imagery are kept as separate visual roles for review.



02 / FEATURES
UltraLow Energy Loss
Our enhanced core construction and premiumgrade materials greatly reduce both noload and load losses. This helps endusers cut operational expenses and delivers longterm energy savings for powerdistribution systems.
Superior Thermal Performance
The oilimmersed cooling system effectively prevents excessive internal temperature rise. It maintains normal internal temperature and enables nonstop operation even under heavyduty cycles or harsh environmental conditions.
Extended Service Life
We adopt a hightightness fullysealed structure. It stops moisture and air from entering the tank, significantly slowing insulation ageing and oxidation. This improves transformer service life and operational reliability.
Low Noise Operation
We apply advanced corestacking technology plus antivibration design to lower operational noise. The transformer fits urban zones, business districts and other noisesensitive installation sites.
High Mechanical Strength
Robust winding construction delivers excellent shortcircuit withstand capability. The transformer retains structural integrity during electrical faults, safeguarding system safety and stable performance.
Minimal Maintenance Requirements
The hermeticallysealed oil tank restricts oil contamination and extends maintenance intervals. It reduces fulllifecycle costs while delivering consistent, dependable longrun performance.
03 / SPECIFICATIONS
Source table retained in full where supplied.
| Product Model | Rated Capacity (kVA) | Vector Group Symbol | HV Voltage (kV) | Tap Range | LV Voltage (kV) | Noload Loss (W) | Load Loss (W at 75℃) | Noload Current (%) | Shortcircuit Impedance (%) |
|---|---|---|---|---|---|---|---|---|---|
| S20 | 30 | Dyn11 | 10 | ±2×2.5% | 0.4 | 70 | 505 | 1.2 | 4 |
| S20 | 50 | Dyn11 | 10 | ±2×2.5% | 0.4 | 90 | 730 | 1.04 | 4 |
| S20 | 63 | Dyn11 | 10 | ±2×2.5% | 0.4 | 100 | 870 | 0.96 | 4 |
| S20 | 80 | Dyn11 | 10 | ±2×2.5% | 0.4 | 115 | 1050 | 0.96 | 4 |
| S20 | 100 | Dyn11 | 10 | ±2×2.5% | 0.4 | 135 | 1265 | 0.88 | 4 |
| S20 | 125 | Dyn11 | 10 | ±2×2.5% | 0.4 | 150 | 1510 | 0.88 | 4 |
| S20 | 160 | Dyn11 | 10 | ±2×2.5% | 0.4 | 180 | 1850 | 0.8 | 4 |
| S20 | 200 | Dyn11 | 10 | ±2×2.5% | 0.4 | 215 | 2185 | 0.8 | 4 |
| S20 | 250 | Dyn11 | 10 | ±2×2.5% | 0.4 | 260 | 2560 | 0.72 | 4 |
| S20 | 315 | Dyn11 | 10 | ±2×2.5% | 0.4 | 305 | 3065 | 0.72 | 4 |
| S20 | 400 | Dyn11 | 10 | ±2×2.5% | 0.4 | 370 | 3615 | 0.64 | 4 |
| S20 | 500 | Dyn11 | 10 | ±2×2.5% | 0.4 | 430 | 4330 | 0.64 | 4 |
| S20 | 630 | Dyn11 | 10 | ±2×2.5% | 0.4 | 510 | 4960 | 0.48 | 4.5 |
| S20 | 800 | Dyn11 | 10 | ±2×2.5% | 0.4 | 630 | 6000 | 0.48 | 4.5 |
| S20 | 1000 | Dyn11 | 10 | ±2×2.5% | 0.4 | 745 | 8240 | 0.48 | 4.5 |
| S20 | 1250 | Dyn11 | 10 | ±2×2.5% | 0.4 | 870 | 9600 | 0.4 | 4.5 |
| S20 | 1600 | Dyn11 | 10 | ±2×2.5% | 0.4 | 1050 | 11600 | 0.4 | 4.5 |
| S20 | 2000 | Dyn11 | 10 | ±2×2.5% | 0.4 | 1225 | 14640 | 0.32 | 5 |
| S20 | 2500 | Dyn11 | 10 | ±2×2.5% | 0.4 | 1440 | 16960 | 0.32 | 5 |
Need a verified configuration or export document package?
Send specification requestBefore quotation, confirm: proof-and-claims.
04 / SELECTION NOTES
Confirm voltage, capacity, frequency, vector group and tap range against the project brief.
Confirm indoor or outdoor placement, cooling, protection and environmental conditions.
Source claims and standards remain subject to final technical and document confirmation.
05 / APPLICATIONS
Confirm the installation environment and electrical requirements for this model.



06 / PROOF
The source document is retained in the private inventory as src-006. Claims, certifications and performance figures marked in the inventory remain pending confirmation before production publication.
Pending confirmation: proof-and-claims.
07 / SERVICE
Share the equipment requirements for a scoped technical conversation.
Send voltage, capacity, quantity and installation conditions.
Confirm drawings, standards, test reports and acceptance requirements.
Discuss installation, commissioning, training and after-sales scope.
08 / RELATED
NEXT STEP
Send voltage, capacity, quantity and installation conditions for a scoped response.
LET’S TALK / JINMA ELECTRIC
Share your requirements with our team.