Electrical scope
Confirm voltage, capacity, frequency, vector group and tap range against the project brief.


PRODUCT DETAIL / DRY-TYPE TRANSFORMERS
10kV / 0.4kV · Non-encapsulated windings · Indoor distribution
01 / OVERVIEW
Read the supplied description before sharing project requirements.
Efficient powersystem construction relies on energysaving, ecofriendly and highly reliable core powerdistribution equipment. We manufacture the Jinma SGB13 nonencapsulated drytype transformer. Built around a nonencapsulated dryinsulation structure, it delivers energy efficiency, compact footprint and enhanced safety. It is engineered for confinedspace indoor urban powerdistribution scenarios, perfectly matching power demands in core city zones, rail transit, commercial complexes and other indoor facilities. Compliant with national energyefficiency and environmental standards, it follows market trends for drytype distribution transformers and serves as preferred equipment for indoor safe power supply and urbangrid upgrading.
Our Jinma SGB13 10 kV nonencapsulated drytype transformer is energysaving and safetyoriented distribution equipment developed for urban indoor powerdistribution applications. It adopts Hclass insulated nonencapsulated windings and an oilfree drytype structure, combining fireproof, explosionproof, lowloss and maintenancefree merits. It works as an ideal alternative to conventional oilimmersed transformers.
At its core is the nonencapsulated drytype design featuring highefficiency energysaving performance. There is zero risk of oil leakage for safer indoor installation, which greatly simplifies fireprotection requirements for distribution rooms. Hclass insulation plus lowloss design enables higher energysaving performance and stable operation, wellsuited for complex urban indoor powerdistribution environments. Strictly complying with national energysaving and environmentalprotection standards with zero pollutant emissions, it fits global greenpowerconstruction requirements. Widely deployed for urban indoor substations, railtransit power supply, commercial complexes and highrise buildings, it keeps seeing rising market demand.
PRODUCT / APPLICATION VIEW
Product photography and application imagery are kept as separate visual roles for review.



02 / FEATURES
Nonencapsulated drycore structure
We adopt nonepoxyresin encapsulated winding construction with excellent heatdissipation capacity. It avoids cracking risks of casting encapsulation layers and delivers stable longterm insulation performance, supporting continuous fullload equipment operation.
Hclass high energy efficiency
The SG(B)13 series follows national Grade1 energyefficiency standards. Both noload loss and load loss are substantially lower than conventional products. Outstanding energysaving performance cuts electricity costs over longtime operation.
Fireproof, explosionproof and ecosafe
Oilfree drytype design delivers noncombustible, nonexplosive performance without leakagecaused pollution. No oil tank or auxiliary firefighting facilities are required. It fits indoor powerdistribution in corecity and denselypopulated zones and meets greenenvironmentalprotection requirements.
Strong shortcircuit resistance & environmental adaptability
Robust winding mechanical strength brings superior shortcircuitshock withstand capability. It copes with complex indoor conditions including high humidity, heavy dust and high altitude, performing anticondensation and anticorrosion for stable and reliable operation.
Intelligent upgrade ready
It supports online temperature monitoring plus remote fault alarm functions. Seamless connection with intelligent powerdistribution systems satisfies smartupgrading demands for urban power grids and boosts powerdistributionmanagement efficiency.
Maintenancefree longcycle operation
Thanks to nonencapsulated drytype sealing design, regular oil replacement, oil filtering and oilquality testing are eliminated. Simplified operation & maintenance workflows greatly reduce OPEX and operational difficulties for urban indoor powerdistribution projects.
03 / SPECIFICATIONS
Source table retained in full where supplied.
| Rated Capacity (kVA) | Vector Group | HV Voltage (kV) | Tap Range | LV Voltage (kV) | Noload Loss (W) | Load Loss (W) @ 120℃ (F) | Noload Current (%) | Shortcircuit Impedance (%) |
|---|---|---|---|---|---|---|---|---|
| 30 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 135 | 640 | 2 | 4 |
| 50 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 195 | 900 | 2 | 4 |
| 80 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 265 | 1240 | 1.5 | 4 |
| 100 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 290 | 1410 | 1.5 | 4 |
| 125 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 340 | 1660 | 1.3 | 4 |
| 160 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 385 | 1910 | 1.3 | 4 |
| 200 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 445 | 2270 | 1.1 | 4 |
| 250 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 515 | 2480 | 1.1 | 4 |
| 315 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 635 | 3120 | 1 | 4 |
| 400 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 705 | 3590 | 1 | 4 |
| 500 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 835 | 4390 | 1 | 4 |
| 630 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 965 | 5290 | 0.85 | 4 |
| 630 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 935 | 5360 | 0.85 | 6 |
| 800 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 1090 | 6260 | 0.85 | 6 |
| 1000 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 1270 | 7310 | 0.85 | 6 |
| 1250 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 1500 | 8720 | 0.85 | 6 |
| 1600 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 1760 | 10500 | 0.85 | 6 |
| 2000 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 2190 | 13000 | 0.7 | 6 |
| 2500 | Yyn0 or Dyn11 | 10/6.3/6 | ±5%; ±2×2.5% | 0.4 | 2590 | 15400 | 0.7 | 6 |
Need a verified configuration or export document package?
Send specification requestBefore quotation, confirm: dry-type-insulation, missing-mentioned-cases, proof-and-claims.
04 / SELECTION NOTES
Confirm voltage, capacity, frequency, vector group and tap range against the project brief.
Confirm indoor or outdoor placement, cooling, protection and environmental conditions.
Source claims and standards remain subject to final technical and document confirmation.
05 / APPLICATIONS
Confirm the installation environment and electrical requirements for this model.



06 / PROOF
The source document is retained in the private inventory as src-007. Claims, certifications and performance figures marked in the inventory remain pending confirmation before production publication.
Pending confirmation: dry-type-insulation, missing-mentioned-cases, proof-and-claims.
07 / SERVICE
Share the equipment requirements for a scoped technical conversation.
Send voltage, capacity, quantity and installation conditions.
Confirm drawings, standards, test reports and acceptance requirements.
Discuss installation, commissioning, training and after-sales scope.
Q: What are the core design advantages of SG(B)1310kV nonencapsulated drytype transformer? A: Its core strengths include nonencapsulated drytype construction, Hgrade high energy efficiency, firesafety & environmentalfriendliness, oilfree safety and maintenancefree running. It is dedicated powerdistribution hardware for urban indoor scenarios.
Q: What scenarios is Jinma SG(B)1310kV nonencapsulated drytype transformer mainly applicable to? A: It is widely used for urban indoor substations, railtransit power distribution, commercial complexes, highrise buildings, hospitals, schools, industrial parks and other indoor safe powerdistribution applications.
Q: Does SG(B)1310kV nonencapsulated drytype transformer comply with national energy efficiency and environmental protection standards? A: Yes. It meets GB 20052 Grade 1 energyefficiency standard. Oilfree and pollutionfree, it fulfils green lowcarbon powerdistribution requirements.
Q: What advantages does the 1310kV nonencapsulated drytype transformer have versus traditional oilimmersed transformers? A: Oilfree fireproof & explosionproof performance, maintenancefree operation, compact dimension, no extra firefighting facilities for indoor installation, plus lower operationandmaintenance costs.
Q: Does Jinma Electric support customization for this product? A: Yes. We can customtune rated capacity, protection grade, cooling method and vector group according to project requirements to satisfy individual indoorpowerdistribution demands.
Q: How difficult is installation and maintenance for SG(B)1310kV nonencapsulated drytype transformer? A: Indoor installation is convenient; no oil pit or explosionproof auxiliary facilities are needed for shorter construction cycles. Nonencapsulated drytype design enables longterm maintenancefree operation and greatly lowers O&M difficulty and expenses.
Q: What is Jinma Electric’s typical lead time? A: We operate a largescale manufacturing base. Standard models finish production, testing and shipment within 1520 days upon contract signing. Customspec units take 2535 days subject to parameter complexity. We provide fullprocess followup to guarantee ontime delivery.
Distribution transformers serve as the voltageconversion backbone for all gridconnected industries. Voltage class, thermal grade and mounting configuration can be custommatched to application requirements.
15 Units 22kV Oilimmersed Transformer Industrial Park Distribution in Vietnam Project
Grid Upgrade Project for 8 35kV Power Transformers in Kazakhstan
20 sets of 11kV oilimmersed transformers grid transformation project in Nigeria
Gridconnected project of 12 PV transformers + ring cabinets in Java, Indonesia
Thailand Bangkok 11 sets of KYN28A24 switchgear + SCB14 drytype transformer complete project
Only project records with supplied detail material have independent routes. Other named references require confirmation.
08 / RELATED
NEXT STEP
Send voltage, capacity, quantity and installation conditions for a scoped response.
LET’S TALK / JINMA ELECTRIC
Share your requirements with our team.